A0200: Emergency power

AHCA cited A0200 177 times at 163 of Florida’s 1,171 small ALFs between July 2023 and July 2026. It’s the tenth most cited tag.

What a surveyor looks at

59A-36.025, F.A.C.

A0200 is the emergency power rule, 59A-36.025. Your home has to be able to keep the air inside at 81 degrees or cooler for at least 96 hours after the power goes out. A home of 16 beds or fewer also has to keep 48 hours of fuel on site.

The plan for all of that is written down, approved by the county and sent to AHCA, and it comes due again every year along with your emergency management plan. Because the rule is about what the home can actually do, a plan on paper isn’t the whole of it.

The paper this tag asks for

There are 8 documents under this tag, and every home needs all of them. Having every one of them is not the same as passing a survey, because a surveyor also reads what’s in them and watches your home run.

Rows marked practice aren’t in the rule’s own words. They’re the paper you keep to show you did what the rule asks, so they’re the likeliest to differ from what a surveyor expects.

Documents every small Florida ALF needs under A0200, the rule that asks for each, and how often each renews.
Every home Renews
Emergency environmental control plan59A-36.025(3)(a) Every year
County approval of the emergency plan59A-36.015(1)(d) Every year
Emergency power policies and procedures59A-36.025(5)(b) No date in the rule
Resident notices about the emergency power plan59A-36.025(8)(b) No date in the rule
Proof the approval was sent to AHCAPractice, not the rule’s words No date in the rule
Generator service and test recordPractice, not the rule’s words No date in the rule
Carbon monoxide alarm59A-36.025(1)(d) No date in the rule
Fuel supply record59A-36.025(1)(b) No date in the rule
The rule’s own words
Emergency environmental control plan, 59A-36.025(3)(a), F.A.C.
Each assisted living facility must maintain a copy of its approved plan in a manner that makes the plan readily available at the licensee’s physical address for review by a legally authorized entity.
County approval of the emergency plan, 59A-36.015(1)(d), F.A.C.
(d) The facility’s emergency management plan, with documentation of review and approval by the county emergency management agency, as described in Rule 59A-36.019, F.A.C., that must be readily available by facility staff.
Emergency power policies and procedures, 59A-36.025(5)(b), F.A.C.
(b) Each assisted living facility shall maintain the written policies and procedures in a manner that makes them readily available at the licensee’s physical address for review by a legally authorized entity.
Resident notices about the emergency power plan, 59A-36.025(8)(b), F.A.C.
(b) Each assisted living facility must maintain a copy of each notification set forth in paragraph (a) above in a manner that makes each notification readily available at the licensee’s physical address for review by a legally authorized entity.
Proof the approval was sent to AHCA, 59A-36.025(3)(b), F.A.C.
(b) Within 30 days of the approval of the plan from the county emergency management agency, the assisted living facility shall submit in writing proof of the approval to the Agency for Health Care Administration to assistedliving@ahca.myflorida.com.
Generator service and test record, 59A-36.025(1)(c), F.A.C.
(c) The acquisition of services necessary to maintain, and test the equipment and its functions to ensure the safe and sufficient operation of the alternate power source maintained at the assisted living facility.
Carbon monoxide alarm, 59A-36.025(1)(d), F.A.C.
(d) The acquisition and maintenance of a carbon monoxide alarm.
Fuel supply record, 59A-36.025(1)(b), F.A.C.
The plan must include information regarding fuel source and fuel storage.

What Alfie does here

Alfie tracks the plan, the county’s approval and the date it’s due again, along with the emergency power policies and the notices residents get about the plan.

No paper shows whether the generator starts, or whether the fuel is really there, and none of it keeps the house at 81 degrees. Run it before hurricane season.